High Sensitivity Smoke Detection System
HomeHome > Products > Smoke Detector > High Sensitivity Smoke Detection System
High Sensitivity Smoke Detection System

High Sensitivity Smoke Detection System

High Sensitivity Smoke Detector system Application FMST-FXV-11E and FMST-FXV-44E series of aspirating smoke detectors pr
Basic Info.
Model NO. FMST-FXV-11E. FMST-FXV-44E
Specification GB
Trademark GQ
Origin China
Production Capacity 100000 PCS/Year
Product Description
High Sensitivity Smoke Detector system
Application
FMST-FXV-11E and FMST-FXV-44E series of aspirating smoke detectors provide very early warning for a wide range of applications including large open spaces, warehouse, IDC etc. This product can support up to 320m and 640m pipe. Patented 3- phase focusing linear laser technology provides a reliable, economic and efficient fire detection solution.
How it works
Air is continually aspirated from protected area through air sampling pipe and is sent into the detector. The sampled air is delivered to a laser detection chamber where smoke particles are detected via light obscuration technology. If smoke is detected, the alarm level will be determined by the level of smoke density and fire alarm thresholds and fire alarm signals will be sent out via relays or device communication interface. All the firm alarm information including smoke concentration, alarm time and which sampling pipe or zone the alarm comes from will be displayed on a built-in LCD.
Each detector supports one alarm zone and contains two independent pipe inlets, two independent airflow sensors, one independent aspirating fan and one laser chamber.
The aspirating fan adopts patented technology to increase aspiration power and decrease noise to minimal level.
FMSTnet
FMST-FXV-11E and FMST-FXV-44E can be connected to FMSTnet where one loop can support up to 252 devices, FMSTnet can support multiple device loops which adopt various communication protocol. FMST-FXV-11E and FMST-FXV-44E has both Rs485 and Ethernet interface and can be configured by FMST-FSC or remotely monitored/controlled by FMST- FSM.FMST-FXV-11E and FMST-FXV-44E supports both Modbus RTU and Modbus TCP/IP protocol.
Modbus communication protocol is open to end-users so that the device can be connected to 3 rd party control system.
Technical specification
ModelFMST-FXV-11EFMST-FXV-44E
DisplayLCDLCD
Water-proof aspirating fan
Maximum number of sampling tubes 2 pipe4 pipe
Power9.36W ( Normal : 0.39A. Alarm :0.44A )18.72W ( Normal : 0.78A. Alarm :0.88A )
Voltage24VDC(18-32 VDC)
IP Level IP50
Working ConditionTemperature: -10ºC~+45ºC. Factory Test : -13°C~58°C. Humidity: 0~95%
Event LogUp to 40000,including fire alarm, fault etc
Sensitivity Range 0.0001 - 20% obs/m. Threshold Settings:Alert Action : 0.0001 - 20% obs/m. Fire1 Fire2 : 0.0001 - 20% obs/m. Fire Delay : 0 - 60s
Communication interfaceModbus-RTU Rs485 interface, Modbus-TCP/IP Ethernet interface
Programming relay6pcs12pcs
Sampling catheter sizeOD : 25mm , ID : 21mm
Maximum sampling catheter length320m640m
Protection Area3200m26400m2
Power Supply Cable2.5 mm 2
Signaling Cable1.5mm2
Smoke Auto-learn & Flow Auto-learnFlow Auto-learn:5 minutes
Smoke Auto-learn:15 minutes - 15 days
Dimensions(W x L x H)1555mm×220mm×86mm320mm×220mm×86mm
Weight1.6kg3kg